Uncategorized

Schaffner Ecosine ® Economy Line FS 42842 Compact Passive Harmonic Filter

Product basic information

Product positioning: Schaffner’s economical passive harmonic filter, belonging to Ecosine ®  The product series focuses on compact design and is suitable for scenarios where harmonic suppression requirements do not exceed 10% THDi (with Ldc), which is different from the Ecosine Evo series (FN 3440/50) that provides high-performance THDi<5%.

Core values:

Compliance: Meets power quality standards such as EN 61000-3-12 and IEEE-519 (Isc/IL<50).

System optimization: Reduce overload and heating caused by grid harmonics, improve power system capacity utilization, reduce system resonance risk and the probability of sensitive electronic equipment shutdown.

Convenient upgrade: Quickly upgrade standard motor drivers to “low harmonic drivers”.

Core technical parameters

Key Explanation of Category Specific Parameters

Rated power 4-160kW (400VAC/50Hz); 5.5~200kW (500VAC/50Hz) Different models correspond to different powers, please refer to the selection table for details

Harmonic suppression performance THDi<10% (with DC Link choke); <15% (without DC Link choke) based on 6-pulse diode rectifier, thyristor rectifier performance varies with trigger angle

Efficiency>98% (at rated line voltage and power), low energy loss, and efficient operation

Overload capacity 1.6x rated current, lasts for 1 minute, adapts to short-term load fluctuations once per hour

Electrical safety withstand voltage P ->E 2500VAC (2 seconds); SCCR=100kA meets electrical safety standards

Rated voltage 3x 380~500VAC ± 10%, suitable for common voltage range of three-phase power grid

The grounding system TN, TT, and IT are compatible with multiple grounding methods and can adapt to different distribution systems

Hardware and environmental specifications

Protection and cooling

Protection level: IP20 (preventing solid foreign objects larger than 12mm from entering).

Cooling method: Internal fan cooling (non adjustable speed) to ensure stable heat dissipation.

Temperature adaptability

Operating requirements for temperature range under working conditions

Normal operation -25 ° C~+45 ° C full power operation

Capacity reduction operation+45 ° C~+70 ° C Capacity reduction formula: Inominal × √ (70 ° C-Tamb)/25 ° C

Transportation/storage -25 ° C~+70 ° C without operating load

Design and reliability

Design standard: The filter complies with UL 61800-5-1 and EN 61800-5-1; The reactor complies with EN 61558-2-20 or EN 60076-6.

Flame retardant rating: UL 94 V-2 and above, reducing the risk of fire.

Mean Time Between Failures (MTBF):>200000 hours (45 ° C/500V, according to Mil-HB-217F standard).

Key points for installation and selection

Installation requirements

Installation position: Directly installed at the input end of the 6-pulse rectifier to suppress harmonics nearby.

Multi load parallel connection: It can connect multiple nonlinear loads (such as multiple motor drivers), and the rated power of the filter needs to match the sum of all load powers.

High power adaptation: When a single filter has insufficient power, multiple filters of the same power model can be connected in parallel to ensure equal current distribution.

Accessory requirements: External UL certified fuses are required (specific model not specified in the document, optional).

Selection principle: Select based on system voltage and load (motor driver) power, and it is not recommended to select based on current rating like EMC/EMI filters.

Mechanical and Connection Specifications

Size and weight: Different models have significant differences in size. The core size (unit: mm) and weight are as follows (selected key models):

|Model | A (length) | B (width) | C (height) | Weight (kg)|

| FS 42842-10-44 | 390 | 185 | 190 | 10 |

| FS 42842-110-35 | 580 | 280 | 248 | 50 |

| FS 42842-210-40 | 700 | 450 | 385 | 100 |

| FS 42842-320-99 | 700 | 450 | 385 | 135 |

Terminal connection: using trap terminals/jumper connectors (A1/B1/C1/A2/B2/C2), compatible with wire specifications and torque:

|Wire specifications (mm ²) | Compatible models | Torque range (Nm)|

| 1.5 | 10/13/16-44 | 1.5 |

| 2.5 | 24/32/38/45-33 | 1.5 |

| 6 | 60/75/90/110-34/35 | 1.5~1.8 |

| 16 | 150/180/210-40 | 4~4.5 |

| 35 | 260-99 | 7~8 |

| 50 | 320-99 | 17~20 |

Typical application scenarios

Motor driver: 6-pulse rectifier front-end driver for general machinery such as pumps and fans.

Battery chargers: industrial battery chargers, electric vehicle DC fast chargers.

Other: All three-phase nonlinear power conversion equipment with 6-pulse diode/thyristor rectifier front-end.

Leave a Reply