EAU-321 is an AutroSafe fire detection system
Product positioning
EAU-321 is a PC/104 specification 4-channel serial communication board for the AutroSafe interactive fire detection system. It is used to interface with third-party devices through the AutroCom protocol and is the core module for external communication.
Core Features
4 independent serial ports, supporting RS232/RS422/RS485 protocols, flexibly defined by jumpers
Support AutroCom redundant communication to enhance reliability
All ports have continuous short-circuit protection
Size: 90mm × 96mm
Working temperature: -40 ℃~+85 ℃
Port function division
Port protocol type function
Port1, Port2 RS232/RS422/RS485 (optional) AutroCom communication, supporting redundancy
Port3 fixed RS232 AutroSafe IFG AutroFieldBus bus communication
Port 4 fixed RS232 AUTROLON network configuration file download

Installation and Capacity Limitations
Installation method: Single machine direct insertion of EAC-300 processor board; Distributed System Stacked EAU-310 Communication Board
Quantity limit: Each system unit only supports 1 EAU-321
Rules for installation quantity:
Battery free host: can accommodate up to 3 communication boards (including EAU-321/310/330)
Battery powered host: can accommodate up to 2 communication boards
When distributed with EAU-310, a maximum of 2 additional modules can be added without batteries; There is a maximum of 1 additional battery
Technical parameters
Parameter values
Number of serial ports 4
Baud rate 9600bps
Communication format: 8 data bits, 1 stop bit, no checksum
Power supply+5VDC ± 10%
Working current 80mA (typical no-load value)
Input impedance (RS232) ≥ 3k Ω
Differential threshold (RS422/485) -0.2V~+0.2V
Wiring terminal 2 × 20 pins (X1, X2)
Jumper configuration
J5/J6: Set Port1/Port2 communication protocol (RS232/RS422/RS485)
J8/J9/J10/J11: All port interrupts are fixed at 7
J7: Set the board address to 100h (both A and B bits are set to In)
Wiring Definition
Provide two 20 pin terminals X1 and X2, respectively defining RS232/RS422/RS485 pins, supporting flat cable connections, RS422/RS485 supports 120 Ω terminal matching (only enabled at the end of the link).
Key issues
What are the functions and protocol differences of the four ports of EAU-321?
Answer: Port1/2 supports RS232/RS422/RS485 jumper switching for AutroCom redundant communication; Port3 is a fixed RS232 responsible for the AutroFieldBus bus bus; Port4 is a fixed RS232, specifically designed for downloading AUTROLON network configurations.
What are the installation quantities and restrictions of EAU-321 in the host?
Answer: Only one EAU-321 can be installed on a single system; A non battery host can accommodate up to 3 communication boards, while a battery host can accommodate up to 2 boards; When distributing EAU-310, if there are no batteries, an additional 2 can be added, and if there are batteries, only 1 can be added.
How to configure the core jumper of EAU-321, and what are the interrupts and addresses?
Answer: Configure the Port1/2 interface protocol for J5/J6; J8/J9/J10/J11 interrupt must be set to 7; J7 fixes the board address to 100h (with bits A and B set to In).