Uncategorized

Bosch Rexroth IndraControl VDP16.3/VDP40.3/VDP60.3 Operation Display Unit Operation Manual

Basic Information

Applicable models: VDP16.3 (12 “), VDP40.3 (15”), VDP60.3 (19 “), excluding versions with CG suffix. Segmented touch version, thin film button version, mixed button touch version.

Target personnel: Mechanical assembly electricians, debugging engineers, equipment maintenance personnel.

Safety warning classification: DANGER (fatal injury), Warning, CAUTION, NOTICE (equipment damage).

Product positioning and permission/prohibition of use

Expected use: Industrial equipment visualization and operation terminal; Used for machine tools, packaging, printing, handling, and woodworking machinery. Original factory specified power supply, cables, and accessories must be used; Unauthorized modification of hardware is prohibited.

Operation of touch screen: Only fingers or Rexroth specific stylus are allowed; Prohibit sharp objects from poking the screen.

Prohibited scenario: Failure to use the accessories and cables specified in the manual may cause equipment damage.

Accessories, spare parts, and vulnerable parts

1) Key component materials

Accessory Material Number Usage

VAC01.1S-YD1 NNNN Y Repeater R911171187: 1 industrial computer drives 2 VDP panels of the same resolution, with a maximum of 4 cascaded

VAP01.1H-W23-024-010-NN 24V power supply R911171065 supplies power to VDP

VAU01.1U-024-024-240-NN UPS R911171024 24V DC uninterruptible power supply

CDI special cable RKB0008 series, with a length of 0.5-50m XVID image+XSER data, requires 2 cables to connect the industrial computer and VDP

USB cable RKB0019 0.5-5m USB signal transmission

Anti interference USB cable RKB0050 1m/3m strong interference environment for use with UPS

2) Vulnerable parts

Backlight LCD backlight: The brightness attenuates to 50% of its original value after approximately 50000 hours at 25 ℃, which is not covered by the warranty. When the lifespan is reached, the backlight component needs to be replaced.

Environmental conditions and technical parameters

environmental conditions

Project operation, transportation, and storage

Temperature+5~+45 ℃ -20~+60 ℃ -20~+60 ℃

Humidity 5-75% RH, no condensation 5-85% RH, no condensation 5-85% RH

Altitude ≤ 3000m——

Vibration impact 10-150Hz; 1g 15g 11ms 15g 11ms

Protection level: IP65 for the front panel, IP20 for the back of the device; Only suitable for installation on control cabinet doors.

Hardware parameters of each model

Model Screen Resolution Power Consumption Current Weight

VDP16.3 12″TFT 800×600 DC24V 20W 0.85A 4.0kg

VDP40.3 15″TFT 1024×768 DC24V 25W 1.05A 5.8kg

VDP60.3 19″TFT 1280×1024 DC24V 40W 1.7A 7.3kg

USB port: maximum 500mA per port; total current of all USB ports is 1A; exceeding this limit will result in power failure protection for the entire device.

Standard: Meets EN61000-6-2/6-4; CE;UL508、CSA C22.2 No.142‑M1987。

Backplane interface definition

Interface Function Description

X1S1 DC24V power supply terminal; 1 pin+24V, 2 pins GND, 3 pins empty

XSER (purple RJ45) CDI data channel (button, touch signal)

XVID (black RJ45) CDI image and video channel, output image

XUSB1-4 rear 4 USB-A ports

XUSBIN USB‑B, Connect the USB signal to the control cabinet PC

S1 DIP dip switch S1-2: OFF cable ≤ 30m; ON cable>30m

M5 screw functional grounding FE must be reliably grounded

Maximum length of CDI cable: VDP16.3 (800 × 600) up to 80m; VDP40.3 (1024 × 768) up to 70m; VDP60.3 (1280 × 1024) up to 60m; Y-Repeater repeater must be used for over length.

USB speed is affected by CDI cable length:

≤ 5m and connected to XUSBIN: USB 2.0 high-speed 480Mbps;

5-30m/>30m enable DIP S1-2: Only 12Mbps full speed, does not support USB HUB hub.

Mechanical installation (cabinet door embedded installation)

Installation requirements

The equipment is installed vertically, with a maximum allowable deviation of ± 45 ° from the vertical;

Reserve 50mm of heat dissipation and wiring space around the equipment;

The installation of cabinet door panels must be flat and free of deformation, otherwise it will damage the IP65 seal of the front panel;

Use 8 M4 bolts to lock from the back of the cabinet; The specified bolt torque is M4=1.4Nm.

Installation hole: The manual provides hole size diagrams for three types of models; Tear off the sealing protective film on the back of the panel and insert it into the cabinet door.

Disassembly steps: Power off → Unplug all wires → Remove nuts → Push the panel forward from the back.

Cable bending requirements: CDI cables must have a minimum of 4 times the cable diameter for a single bending; Repeatedly move at least 8 times the diameter of the cable.

Wiring taboos: CDI signal lines are strictly prohibited from running parallel to motor power cables, as it may cause image interference.

Key points of electrical wiring

Power supply: An isolated 24V industrial power supply must be used; Recommend VAP01.1H.

Functional FE is crucial: the VDP panel and the control cabinet PC must be directly interconnected in terms of functional FE; If only a single device is powered off, the potential difference will directly burn out the board circuit.

CDI wiring sequence: Connect functional ground FE first; XSER purple XSER; XVID Black – XVID; Two cables cannot be reversed.

Two options for UPS configuration

Plan A: Control cabinet PC+VDP display all connected to UPS output; The panel can still be operated during power outage to achieve safe shutdown;

Option B: Only the control cabinet PC is connected to UPS, and the VDP is directly 24V; the screen goes black when the power is cut off.

When the cable distance is greater than 50m, an isolated power supply must be selected to prevent common mode circulating current.

Equipment buttons and LED status indicator lights

button layout

L1-L8, R1-R8: M machine tool function keys on both sides; It can be used as a USB keyboard encoding output, and can also output bit signals through PROFIBUS-DP via PCI board;

OP2-OP9 operation keys, F2-F9 function keys Prog、Info; There are two modes for key encoding (UpperClassFilter on/off).

Front panel LED status light

LED status meaning processing

Power green constant on, power supply and communication are normal

Turn off the 24V power supply and check the power supply

Flashing green and disconnecting communication with the control cabinet PC to check the CDI cable; Y – Repeat represents inactive panel

HDD yellow constantly flashing industrial control computer hard disk read and write; SMART hard drive alarm status requires replacement of industrial computer hard drive

Temp red flashing control cabinet PC fan fault; Always on>50 ℃, overheating reduces the temperature inside the cabinet, and the fan needs to be repaired

UPS red bright red industrial computer is running in UPS battery mode. When the mains power is lost, restore the mains power and perform a safe shutdown and restart

Tip: The LED status actually depends on the connected cabinet PC, and some PC models do not support all alarm outputs.

Debugging and troubleshooting

Debugging: After the hardware is connected and powered on, there is no need to configure the VDP itself; The resolution is automatically recognized by the control cabinet PC when powered on; Note: Hot swapping to replace VDP can only replace panels with the same resolution; The resolution is only detected during the startup phase of the PC, and the screen cannot display normally when changing to a different resolution during runtime.

Fault phenomenon handling plan

Completely no image confirmation of 24V power supply; VDP power on timing shall not be later than the industrial computer; Check two CDI cables XVID/XSER; Graphics card driver output setting VDP mode

Resolution error PC graphics card driver setting correct resolution, restart control cabinet PC

USB device does not work/touch failure. Set the S1-2 dip switch according to the CDI cable length; Touch screen to perform calibration

​Maintenance and upkeep

Maintenance cycle: Check the fastening status of all terminal plugs annually and inspect cables for any compression or damage.

Cleaning: Do not use solvents, diluents, or high-pressure water guns; Wipe the panel with a soft cloth.

Backlight lifespan management: Windows power options set the backlight off time to extend the backlight lifespan; Backlight dimming can only be replaced by contacting Rexroth service.

All screws must be disassembled strictly in accordance with the manual torque, as incorrect torque can damage the IP protection level.